MAN0871-02 21 AUGUST 2007 PAGE 1
Specifications / Installation HE-XT103-10
1 Specifications
HE-XT103-10 Specifications
Digital DC Inputs XLT103-10
Digital DC
Outputs
XLT103-10
Inputs per Module
12 including 4 configurable
HSC inputs
Outputs per
Module
12 including 2 configurable
PWM outputs
Commons per
Module
1
Commons per
Module
1
Input Voltage
Range
12 VDC / 24 VDC Output Type Sourcing / 10 K Pull-Down
Absolute Max.
Voltage
35 VDC Max.
Absolute Max.
Voltage
28 VDC Max.
Input Impedance
10 k
Output
Protection
Short Circuit
Input Current
Positive
Logic
Negative Logic
Max. Output
Current per
point
0.5 A
Upper Threshold 0.8 mA -1.6 mA
Max. Total
Current
4 A Continuous
Lower Threshold 0.3 mA -2.1 mA
Max. Output
Supply Voltage
30 VDC
Max Upper
Threshold
8 VDC
Minimum Output
Supply Voltage
10 VDC
Min Lower
Threshold
3 VDC
Max. Voltage
Drop at Rated
Current
0.25 VDC
OFF to ON
Response
1 ms
Max. Inrush
Current
650 mA per channel
ON to OFF
Response
1 ms Min. Load None
HSC Max.
Switching Rate
10 kHz Totalizer/Pulse,Edges
5 kHz Frequency/Pulse,Width
2.5 kHz Quadrature
OFF to ON
Response
1 ms
Thermistor
Inputs, Medium
Resolution
XLT103-10
ON to OFF
Response
1 ms
Number of
Channels
2
Output
Characteristics
Current Sourcing (Pos logic)
General Specifications
Input Ranges
Safe input voltage
range
Input Impedance
(Clamped @ -0.5
VDC to 12 VDC)
10K OHM
Thermistor
Half Bridge
9.59K ohm pulled up to
4.8 VDC
Required Power
(Steady State)
150 mA @ 24 VDC
Required Power
(Inrush)
30 A for 1 ms @ 24 VDC
Nominal Resolution
%AI at 10K Ohm
10 Bits
15,008 counts
Primary Power
Range
10 – 30 VDC
Conversion Speed
All channels converted once
per ladder scan
Relative Humidity
5 to 95% Non-
condensing
Max. Error at 25°C
reading / ambient
±0.5°F or ±0.3°C
Using specified linearization
in ladder program
Operating
Temperature
-10°C to +60°C
Terminal Type
Screw Type,5 mm
Removable
Additional error for
reading / ambient
temperatures other
than 25°C
TBD
CE
UL
See Compliance Table at
http://www.heapg.com/Support/compliance.htm
Filtering
160 Hz hash (noise) filter
1-128 scan digital running
average filter
Weight 12.5 oz. (354.36 g)
Clock Accuracy +/- One Minute/Month at 20C
2 Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm.
3 Ports / Connectors / Cables
Note: The case of the XLE is black, but for clarity, it is shown in a
lighter gray color.
Want More Information?
To download the XLE User
Manual (MAN0863), refer
to Technical Support in this
document.
3.622 [92mm]
3.622 [92mm]
001XLE002
Refer to XLT User
Manual (MAN0863) for
panel box information
and a handy checklist of
requirements.
Note:
The tolerance to meet
NEMA standards is
± 0.005” (0.1 mm).
To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit.
Lift lid.
CAUTION: Do not over tighten
screws when screwing the lid
back on.
001ACC009
Power Connector
Power Up:
Connect to Earth Ground.
A
pply 10 – 30 VDC.
Screen lights up.
CAN Connector
Use the CAN Connector
when using CsCAN network.
I/O Jumpers (Not Shown): I/O Jumpers (JP) are located
internally. To access, remove back cover of unit.
Wiring Connectors (J1 – J4), I/O Jumpers (JP1-3), and DIP
Switches (RS-485) are described in the DIP Switches, Wiring
and Jumpers section of this document.
XLT OCS Model: HE-
X
T103-10
12 Digital DC Inputs / 12 Digital Outputs
2 10K Thermistor Inputs
MJ1
(RS-232 / RS-485)
MJ2
(RS-232 / RS-485)
J1
I/O
Jumper
Memory Slot
001XLE029-R2
J2
I/O
Jumper
NET 1
(CsCAN)
Power
DIP
Switch
Note: The highest usable frequency is 65 KHz for the PWM output
Przeglądanie stron 0
1 2 3 4

Podsumowanie treści

Strona 1 - T103-10

MAN0871-02 21 AUGUST 2007 PAGE 1 Specifications / Installation HE-XT103-10 1 Specifications HE-XT103-10 Specifica

Strona 2 - 12-24VDC

PAGE 2 21 AUGUST 2007 MAN0871-02 XLT103-10 Specifications / Installation Section 3 continued

Strona 3

MAN0871-02 21 AUGUST 2007 PAGE 3 Specifications / Installation XLT103-10 5 Analog Conditioning 5.1 Filter Filt

Strona 4

PAGE 4 21 AUGUST 2007 MAN0871-02 XLT103-10 Specifications / Installation 7. Safety When found on the product, the