MAN0947-01-EN Specifications / Installation
1/6/2011 Page 1 of 3
1 Specifications
12 including 4
configurable HSC inputs
24 including 4
configurable HSC inputs
12 including 2 configurable
PWM outputs
16 including 2 configurable
PWM outputs
Sourcing / 10 K Pull-Down
0.5 A per point, 4A total (continuous)
Min./Max. Output
Supply Voltage
10 VDC (min), 30 VDC (max)
Max. Voltage Drop at
Rated Current
10 kHz Totalizer/Pulse,Edges
5 kHz Frequency/Pulse,Width
2.5 kHz Quadrature
Current Sourcing (Pos logic)
Analog Inputs, Medium Resolution
Analog Inputs, Medium Resolution
All channels converted every ladder scan
Max. Error at 25°C (excluding zero)
Current Mode: 1.00%
Voltage Mode: 0.50%
Input Impedence
(Clamped at -0.5 to +12Vdc)
160Hz hash (noise) filter
1-128 scan digital running average filter
XL Series Built-in I/O – Model 3 & Model 4 I/O
Model 3: 12 DC Inputs, 12 DC Outputs, 2 Analog Inputs
Model 4: 24 DC Inputs, 16 DC Outputs, 2 Analog Inputs
for XLe, XLt, XL6 (all models) and XL10e
Wiring Specifications
For I/O wiring (discrete), use the
following wire type or equivalent: Belden
9918, 18 AWG (0.8 mm
2
) or larger.
For shielded Analog I/O wiring, use the
following wire type or equivalent: Belden
8441, 18 AWG (0.8 mm
2
) or larger.
For CAN wiring, use the following wire
type or equivalent: Belden 3084, 24
AWG (0.2 mm
2
) or larger.
Use copper conductors in field wiring
only, 60/75° C
Location of I/O jumpers
(JP1 & JP3) and
wiring connectors
(J1, J2, J3 & J4) with back
cover removed.
Note: The Cscape Module Setup configuration must match the
selected I/O (JP) jumper settings.
Note: When using JP3 (A1-A2), each channel can be
independently configured.
20mA 10VDC
JP3
CURRENT OR VOLTAGE INPUTS
001XLE043-R1
A1
A2
A1
A2
11 22
33 44