MAN0885-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
3/2/2010 Page 5 of 6 #1037
4.5 Power Port and Wiring
5 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the
appropriate jumper option.
5.1 I/O Jumpers Settings (JP1 - JP2)
5.2 Wiring Examples
J1 Orange
Terminal
Connector
Name
I1 IN1
I2 IN2
I3 IN3
I4 IN4
I5 IN5
I6 IN6
I7 IN7
I8 IN8
H1 HSC1 /IN9
0V Ground
A1 Analog IN1
A2 Analog IN2
A3 Analog IN3
A4 Analog IN4
0V Ground
J2 Black
Terminal
Connector
Name
C6 Relay 6 COM
R6 Relay 6 NO
C5 Relay 5 COM
R5 Relay 5 NO
C4 Relay 4 COM
R4 Relay 4 NO
C3 Relay 3 COM
R3 Relay 3 NO
C2 Relay 2 COM
R2 Relay 2 NO
C1 Relay 1 COM
R1 Relay 1 NO
H4 HSC4 / IN12
H3 HSC3 / IN11
H2 HSC2 / IN10
6 Filter
Filter Constant sets the level of digital filtering according to the following chart.
Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Filter Constant)
on module response to a temperature change.
Primary Power Port Pins
Pin Signal Description
1 Ground Frame Ground
2 V- Input Power Supply Ground
3 V+ Input Power Supply Voltage
I1
0V
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XL6 HEXL102
can be wired for Positive Logic
inputs or Negative Logic inputs.
0V ON J1
R2
C2
R3
C3
R6
C6
R4
C4
R5
C5
R1
C1
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
230VAC
OR
25VDC
N
L
230VAC
OR
25VDC
N
L
OR
25VDC
N
L
OR
25VDC
N
L
J2 Black
Positive Logic
Digital In / Relay Out
Wiring Specifications
For I/O wiring (discrete), use the following wire type or
equivalent: Belden 9918, 18 AWG (0.8 mm
2
) or larger.
For shielded Analog I/O wiring, use the following wire type or
equivalent: Belden 8441, 18 AWG (0.8 mm
2
) or larger.
For CAN wiring, use the following wire type or equivalent:
Belden 3084, 24 AWG (0.2 mm
2
) or larger.
Use copper conductors in field wiring only, 60/75° C
J1 Orange
Positive Logic In
Digital In /
Analog In
I1
I2
I3
I4
0V
A1
A2
0V
I5
I6
I7
I8
A3
A4
H1
12-24VDC
Note:
Loop Power requirements are determined
by the transmitter specification.
J1
JP2
JP1
20
0
10
100
90
80
70
60
50
40
30
1 2 3 4 5
0 7
Filter
Location of I/O jumpers (JP2 and JP1) and wiring
connectors
(J1 and J2).
Note:
When using JP2 (A1-A4), each channel can be independently
configured.
Note:
The Cscape Module Setup configuration must match the selected
I/O (JP) jumper settings.
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Default
A1
A2
A3
A4
JP2 Analog In (A1 – A4)
Current Voltage
(20 mA) (10 V)
Default
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
Komentarze do niniejszej Instrukcji