MAN0703-01 24 SEP 2003 PAGE 5
11.5 SmartStix I/O Default Operation
SmartStix I/O has been designed so that its default operation satisfies the most common applications.
This keeps the user interface simple and makes the product easy to use. The default operation is
summarized in Table 2. To change the default operator, see Advanced SmartStix Programming (Section
3).
Table 2 – SmartStix Analog I/O Default Operation
Amalog Input Devices
Data Reporting Method Every 500 milliseconds
Heartbeat Generation Interval 1000msec.
Analog Output Devices
Update Method
(using NETPUT Remote I/O Function block)
Updated by each Consumed
Directed Analog Data
transmission
Heartbeat Generation Interval 1000msec.
(LET) Life Expectance Time
(Receipt of Heartbeat)
2000msec.
(LET) Action Upon Expiration Turn all outputs OFF