PAGE 4 24 SEP 2003 MAN0703-01
Table 1 - Consumed / Produced Parameter Descriptions
Consumed Directed
Digital Data Words
Function
Affects
Word 1 (bits 1 to 16) Voltage/Current Mode, Input Filter Control All Analog Modules
Word 2 (bits 17 to 32) Scale factor All Analog Modules
Word 3 (bits 33 to 48) Specifies whether SmartStix uses default
configuration or values from Word 4.
All Analog Modules
Word 4 (bits 49 to 64) Sets digital inputs / heartbeat and life
expectancy time data.
All Analog Modules
Word 5 (bits 65 to 80) Sets the default state of Analog outputs. Modules with Analog Outputs
Produced Global
Digital Data Words
Function
Affects
Word 1 (bits 1 to 16) Reserved
Word 2 (bits 17 to 32) Reserved
Word 3 (bits 33 to 48) Status bits and diagnostic data All Analog Modules
Word 4 (bits 49 to 64) Device class number and firmware identifier
sent by SmartStix module.
All Analog Modules
Function Consumed Directed
Analog Data Words
HE550MIX977 HE550DAC207
Affects
Word 1 Output Channel 1 Data Output Channel 1 Data Modules with Analog Outputs
Word 2
Output Channel 2 Data Output Channel 2 Data
Modules with Analog Outputs
Word 3
Output Channel 3 Data Output Channel 3 Data
Modules with Analog Outputs
Word 4
Output Channel 4 Data Output Channel 4 Data
Modules with Analog Outputs
Word 5
Output 1 Default Data Output Channel 5 Data
Modules with Analog Outputs
Word 6
Output 2 Default Data Output Channel 6 Data
Modules with Analog Outputs
Word 7
Output 3 Default Data Output Channel 7 Data
Modules with Analog Outputs
Word 8
Output 4 Default Data Output Channel 8 Data
Modules with Analog Outputs
Word 9 Not used
Output 1 Default Data
Modules with Analog Outputs
Word 10 Not used
Output 2 Default Data
Modules with Analog Outputs
Word 11 Not used
Output 3 Default Data
Modules with Analog Outputs
Word 12 Not used
Output 4 Default Data
Modules with Analog Outputs
Word 13 Not used
Output 5 Default Data
Modules with Analog Outputs
Word 14 Not used
Output 6 Default Data
Modules with Analog Outputs
Word 15 Not used
Output 7 Default Data
Modules with Analog Outputs
Word 16 Not used
Output 8 Default Data
Modules with Analog Outputs
Function Produced Global
Analog Data Words
HE550MIX977 HE550ADC970
Affects
Word 1 Input Channel 1 Data Input Channel 1 Data Modules with Analog Inputs
Word 2
Input Channel 2 Data Input Channel 2 Data
Modules with Analog Inputs
Word 3
Input Channel 3 Data Input Channel 3 Data
Modules with Analog Inputs
Word 4
Input Channel 4 Data Input Channel 4 Data
Modules with Analog Inputs
Word 5
Input Channel 5 Data Input Channel 5 Data
Modules with Analog Inputs
Word 6
Input Channel 6 Data Input Channel 6 Data
Modules with Analog Inputs
Word 7
Input Channel 7 Data Input Channel 7 Data
Modules with Analog Inputs
Word 8
Input Channel 8 Data Input Channel 8 Data
Modules with Analog Inputs
Word 9 Not used
Input Channel 9 Data
Modules with Analog Inputs
Word 10 Not used
Input Channel 10 Data
Modules with Analog Inputs
Word 11 Not used
Input Channel 11 Data
Modules with Analog Inputs
Word 12 Not used
Input Channel 12 Data
Modules with Analog Inputs
Note: Table 1 summarizes SmartStix I/O analog module consumed and produced data words. For
advanced users, refer to Section Three: Advanced Programming for explanations describing
consumed and produced words in detail.
Komentarze do niniejszej Instrukcji