If a directory name is highlighted, pressing Enter will switch to that directory showing its files and sub-
directories. In a sub-directory, highlighting.. (dot dot) and pressing Enter will move up one directory.
Fail Safe System
The Fail-Safe System is a set of features that allow an application to continue running in the event of
certain types of "soft" failures. These "soft" failures include:
Battery power loss
Battery-Backed Register RAM or Application Flash corruption due to, for example, an excessive
EMI event.
Selecting “Fail-Safe System” menu will open the following menu screen:
Selecting Backup/Restore Data displays the following screen in:
Backup
= Copies Battery Backed RAM contents on to the onboard FLASH memory of the OCS.
Restore
= Copies the backed up data from onboard FLASH to the battery backed RAM.
Clear Backup
= The backup data will be erased from the onboard FLASH.
Exit
= Goes back to previous menu