MAN0967-01-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________________
8/24/2012 #1037
4.2 External DIP Switch Settings
MJ2 Pinouts in Half and Full Duplex Modes
4.3 CAN Network Port and Wiring
Table - Ports and Functions
Ladder function
controlled
Serial Downloable
Protocols
NET1 Port Pin Assignments
4.1 Serial Communications:
MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.
As seen when looking at the side of the XL10 unit:
The DIP Switches are used for
termination of the RS-485 ports. The
XL10 is shipped un-terminated.
To terminate, select one of the DIP
Switches and configure it based upon
the option that is desired.
SW1 - ON enables MJ2 RS485 port termination (121 Ohms).
OFF disables MJ2 RS485 port termination.
SW2 & SW3 - ON places MJ2 RS485 port in half-duplex mode.
OFF places MJ2 RS485 port in full-duplex mode.
SW4 - ON enables MJ1 RS485 port termination (121 Ohms).
OFF disables MJ1 RS485 port termination.
CAN Connector
Use the CAN Connector when
using CsCAN network.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)