PAGE 4 12 May 2011 MAN0951-02
HE-559ACM300
Information is subject to change without notice.
4 NETWORK DATA
Consumed Digital Data – This data is sent from the controller to the SmartBlock. For typical
applications the I/O configuration setup in Cscape will automatically populate this data. For more
advanced applications you may use NetPut functions to write this data. Please see the advanced
programming guide MAN0880 for more details.
Q1 override
Upon module stop / timeout, if Q1 override is true, Q1 is set to Q1 default, otherwise the Q1
value is held. This override / hold polarity is consistent with OCS / Cscape usage but the
reverse of the legacy analog hold / override polarity in word 5.
Frequency Source, Set for phase B, Clear for phase A or C
Frequency Source, Set for phase C, Clear for phase A or B
Always accumulate Watt-Hours
Do not accumulate Watt-Hours if load is under 0.005% of full scale to avoid meter
creep due to slight zero errors
Set to report period instead of frequency in AI13 / AI14
Relay output, set to ON to close N.O. and open N.C contacts.
Set to ON to clear KWhr, set to OFF to re-enable KWhr accumulator
Set to ON to clear Status flags, set to OFF to re-enable Status flags
Produced Digital Data – This data is sent from the SmartBlock to the controller. Normally this data is
mapped into specific registers in the I/O configuration in Cscape. For advanced applications NetGet
functions can be used to obtain this data. Since this data is broadcast to all controllers on the network
additional controllers can use NetGet functions to obtain this data as well.
Watt-Hour accumulator half full.
VAR-Hour accumulator half full
Zero Cross timeout on Phase A
Zero Cross timeout on Phase B
Zero Cross timeout on Phase C
Zero Cross detected on Phase A
Zero Cross detected on Phase B
Zero Cross detected on Phase C
5V supply rail under 4 volts
Peak voltage level exceeded
Peak current level exceeded
Sign changed occurred in Watt calculation
Sign changed occurred in VAR calculation